Product name : “SHURE” CO carbon monoxide sensor transmitter combustible gas pollution detector RS485,4-20mA,0-5V,0-10V
Power supply: 10~30VDC (for 0-10V output equipment, only 24V power supply can be used)
Average power consumption: 0.18W
Temperature measurement range: -40°C~+80°C
Humidity measurement range: 0~100%RH
Temperature accuracy: +0.5°C
Humidity accuracy: +3%RH
CO resolution: 1ppm
CO Accuracy: ±5ppm or ±10%
Zero drift: ±3ppm
Working temperature: -20~50°C
Working humidity: 15~90%RH non-condensing
Stability: ≤2% signal value/month
Response time: <30s
Preheating time: ≥5min
Repeatability: <2%
Pressure range: 90~110kPa
Output signal: RS485|4-20mA|0-5V|0-10V